A thermal camera measures surface temperature, nothing else. It does not see inside a sealed panel, it does not see through a closed door, and on a Dubai afternoon it will happily show you the sun instead of your fault. Used correctly it finds a loose connection weeks before it burns; used carelessly it produces a colourful picture and a number nobody can defend. This page is how to tell the two apart — before you pay anyone, including us.
Panel thermography with WOLKER is AED 6,500 per survey. The survey covers the switchboards of a single facility within Dubai, walked as one repeatable route; sites with several buildings are quoted per facility. Prices exclude 5% VAT; other emirates on request.
Infrared is a surface measurement. Everything else follows from that.
There is no UAE law fixing an inspection frequency for private commercial buildings. What exists is engineering practice, and it is unusually specific.
| Source | What it sets |
|---|---|
| NFPA 70B — since the 2023 edition a Standard for Electrical Equipment Maintenance, no longer a Recommended Practice | Infrared thermography of electrical equipment at intervals not exceeding 12 months, and at least every 6 months for equipment in Condition 3 — the class that includes equipment where urgent action was identified in a previous scan (FLIR; sections 9.3.1.2 / 9.3.3.1 / 9.3.1.4 per IRINFO) |
| ANSI/NETA MTS, Appendix B — frequency of maintenance tests | Metal-enclosed busways: “Infrared Only — 12” months, adjusted by the equipment condition and reliability matrix (ANSI/NETA MTS Appendix B, p. 244) |
| ISO 18436-7 — qualification of thermography personnel | Three categories of thermographer; a Category 1 holder “shall not be responsible for the choice of test method or technique to be used, nor for the assessment of test results”, and category minimums run 12 / 24 / 48 months of logged experience (BINDT PCN CM/IRT, Issue 8, 2025, §2.2–2.4 and Table 2; standard: ISO 18436-7:2014) |
Read together, the practical rule for a Dubai facility is: once a year for everything electrical, twice a year for anything that has already given you a finding, and immediately before the summer peak rather than after it. Certification is voluntary in the UAE — but it tells you who is allowed to interpret the picture, which matters more than who is allowed to take it.
Most people receiving a thermography report look at the colours. The colours are the least informative part. Six things decide whether the report is worth anything.
Once those are present, severity is a table, not an opinion. The criteria widely used for electrical work, reproduced from NETA in the Infraspection Institute standard §10.1:
| Priority | ΔT vs similar component, similar load | ΔT over ambient air | Recommended action |
|---|---|---|---|
| 4 | 1–3 °C | 1–10 °C | Possible deficiency; warrants investigation |
| 3 | 4–15 °C | 11–20 °C | Probable deficiency; repair as time permits |
| 2 | — | 21–40 °C | Monitor until corrective measures can be accomplished |
| 1 | >15 °C | >40 °C | Major discrepancy; repair immediately |
Note what this table implies: a 12 °C difference between two identical breakers on the same load is more serious than a panel that is simply warm. Absolute temperature sells reports; difference against a reference is what engineers act on.
We do the pre-screening layer, walked as a repeatable route so this quarter’s readings can be compared with last quarter’s rather than argued about. Every finding is delivered with the thermal frame and the plain photograph it came from, and the report is fingerprinted when it is issued — meaning anyone you hand it to can check months later that the file is the one we issued and no reading was adjusted after a disagreement. Findings reach you within 48 hours of the visit. Here is the report taken apart, page by page.
What we do not do: formal, insurer-facing electrical certification is issued by accredited inspection bodies; we coordinate that with a partner rather than pretend we can issue one. We also do not sell you the repair — we have nothing to gain from finding more faults than exist.
| Panel Thermography — radiometric thermal pre-screening of your switchboards, hotspots photographed, measured and logged on one repeatable route | AED 6,500 · per survey |
| Electrical Integrity package — thermography plus the acoustic partial-discharge survey on the same route. Heat is seen before it becomes an outage; discharge is heard before it becomes heat | AED 15,900 combined — against AED 19,000 booked separately (AED 6,500 + AED 12,500) |
| HVAC & Refrigerant Check — thermal and gas inspection of chillers, cold rooms and HVAC plant | AED 4,500 · per visit — what it covers |
The survey covers the switchboards of a single facility within Dubai, walked as one repeatable route; sites with several buildings are quoted per facility. Prices in AED, exclude 5% VAT, cover a single facility within Dubai; other emirates on request. Slots are booked in order of enquiry. Full price list →
Panel thermography is AED 6,500 per survey with WOLKER, fixed, and an HVAC and refrigerant thermal check is AED 4,500 per visit. Booked with the acoustic partial-discharge survey on the same route, thermography comes to AED 15,900 combined instead of AED 19,000 separately, because it is one visit and one report. Prices exclude 5% VAT and cover a single facility within Dubai.
Since its 2023 edition NFPA 70B is a Standard rather than a Recommended Practice, and it sets infrared thermography of electrical equipment at intervals not exceeding 12 months, tightening to at least every 6 months for equipment where urgent action was identified in a previous scan. ANSI/NETA's maintenance frequency table lists infrared inspection of metal-enclosed busways at 12 months, adjusted by equipment condition. No UAE law fixes a frequency for private commercial buildings.
Anything that is not on a surface in its line of sight. It cannot see through panel doors, dielectric barriers or plastic guards, all of which are opaque to infrared, so enclosures have to be opened or fitted with IR windows. It also needs the equipment energised and under normal load — a fault that only appears at 90% load is invisible at 20%.
The written report should state the thermographer's certification level and number, the imager's make, model and serial, the load at the time of the survey, the emissivity and reflected temperature used, the reference the temperature difference is measured against, a list of equipment that was not inspected, and for each finding both a thermogram and a visible-light photograph. Without those, the temperature in the report cannot be checked or repeated.
No. Formal insurer-facing electrical certification is issued by accredited inspection bodies; we coordinate that with a partner when you need it. Our thermal work is pre-screening between those formal inspections — it finds the problem early, documents it and gives you a file that can be verified later.
For loose connections and overloaded joints, usually. For partial discharge in switchgear, no — discharge is audible in ultrasound long before it becomes heat, so an acoustic array catches it earlier. Two ways of catching the same failure; we run them on one visit.
Panel thermography is AED 6,500 per survey. The survey covers the switchboards of a single facility within Dubai, walked as one repeatable route; sites with several buildings are quoted per facility. Prices in AED, exclude 5% VAT, cover a single facility within Dubai; other emirates on request.